Application:
0.6/1kV PVC Cable, It to be used for indoors, in tunnel, in down wells,cable furrow or pipe, underground.
Note: the single core armored cables are used for D.C. system only. As for A.C. system, armor layer should be used of non-magnetic material or magnetic isolation measures.
Standards: BS 7870-3.10-2001 or IEC 60502 -1
Conductor: Cu or Aluminum Insulation:PVC Sheath: PVC
Sheath Color: Black or Colors

Cable Structure:
1. Conductor: Copper(Cu) or Aluminum
2. PVC insulation
3. Fill layer
4. Around the package tape
5. Inner Sheath
6. Steel tape armor
7. Outer Sheath
8. Mark
Product Description:
- PVC insulated PVC sheathed power cable (PVC/PVC Cable)
- PVC insulated steel tape armored PVC sheathed power cable (PVC/STA/PVC Cable)
- PVC insulated steel wire armored PVC sheathed power cable (PVC/SWA/PVC Cable)
- Flame retardant PVC insulated PVC sheathed power cable (FR/PVC/PVC Cable)
- Flame retardant PVC insulated steel tape armored PVC sheathed power cable (FR/PVC/STA/PVC Cable)
- Flame retardant PVC insulated steel wire armored PVC sheathed power cable (FR/PVC/SWA/PVC Cable)
FR – Flame Retardant
Number of Cores & Nominal Cross-section Area
|
Number of Cores |
1 |
2 |
3 |
3+1 |
4 |
3+2 |
4+1 |
5 |
|
Section Area (mm2) |
4 - 500 |
2.5 - 500 |
2.5 - 300 |
4 - 300 |
2.5 - 300 |
2.5 -300 |
4 - 300 |
2.5 - 95 |
More about
0.6/1kV PVC Cable style, Plz contact our
team. We'll gvie reply ASAP.
Main Properties:
|
No. |
Test Item |
Property |
|
1 |
Construction |
Listed to the tables |
|
2 |
Conductor resistance |
Listed to the tables |
|
3 |
Test Voltage |
A.C 3.5kV 5min |
No breaken |
|
4 |
Machenical Properties before aging |
Tensile Strength |
Insulation |
Min. 12.5N/mm2 |
|
Sheath |
Min. 12.5N/mm2 |
|
Elongation at break |
Insulation |
Min. 150% |
|
Sheath |
Min. 150% |
|
Machenical properties after aging |
Tensile Strength |
Insulation |
100℃±2℃7days Min. 12.5N/mm2 |
|
Sheath |
100℃±2℃7days Min. 12.5N/mm2 |
|
Varying valve of tensile strength |
Insulation |
100℃±2℃7days Max. 25% |
|
Sheath |
100℃±2℃7days Max. 25% |
|
Elongation at break |
Insulation |
100℃±2℃7days Min.150% |
|
Sheath |
100℃±2℃7days Min.150% |
|
Varying valve of tensile strength |
Insulation |
100℃±2℃7days Max. 25% |
|
Sheath |
100℃±2℃7days Max. 25% |
|
5 |
Flame retardant property |
IEC60332 - 3 |
|
6 |
Constant of insulation resistivity |
Min at 20℃ |
36.7 |
|
Ki MΩ.km |
Min at 70℃ |
0.037 |
Installation:
1. The installation temperature should not over 20℃, If the ambient temperature is lower than 0℃, the cable should be preheated.
2. The bending radius of cable should not less than 8 times.
3. After installantion, the cable should with stand voltage test for 15min. 3.5kv D.C.
In air:
1. As the single core cable laying in parallel, the distance between the cable’s center is 2 times (for cables which cross section area of conductor ≤185mm2) and
90mm (for cables which cross sectional area of conductor≥240mm2)
2. Ambient temperature: 30℃
3. Max. temperature of conductor: 70℃
4. Rating factors of current rating for ambient temperature:
|
Air temperature |
20℃ |
25℃ |
35℃ |
40℃ |
45℃ |
|
Rating factors |
1.12 |
1.06 |
0.94 |
0.87 |
0.79 |
Direct in ground:
1. When the single core cables are installed separately, the distance between the cable’s center is 2 times of the cable diameter.
2. Ambient temperature: 25℃.
3. Max. temperature of conductor: 70℃.
4. Soil thermour resistivity: 1.0℃. m/w.
5. Depth: 0.7m
6. Rating factors under different ambient temp.:
|
Air temperature |
15℃ |
20℃ |
30℃ |
35℃ |
|
Rating factors |
1.11 |
1.05 |
0.94 |
0.88 |
Short ciruit ratings:
|
Max temperature at short circuit |
Max temperature short circuit rating |
|
130℃ |
I=94 S√A |