Bookmark
Print
Contact
Chat
FAA-L-824 Underground primary cable for Airport lighting circuits
Type C : Copper tape screened 5 kV
Reference standard : FAA AC 150/5345-7E
Construction:
1. Stranded tinned copper conductor
2. Extruded semi-conducting compound
3. XLPE Insulation
4. Semi-conducting tape, helically applied
5. One lay of copper tape, helically applied, 30%
Overlapping
6. Separation tape
7. PE outer sheath - black
Properties:
1. Abrasion resistant、Oil resistant、UV resistant、Deicer resistant (FR/KAc) 、Halogen-free
2. Service temperature: -40 ... +85 °C
(for a max. current of 6.6 A)
3. Min. bending radius: 12x outer diameter
4. Max. pulling force: copper cross-section (in mm2) x 50 N/mm2
5. Min. laying temperature: -10 °C
Dimensions:
|
Cross-section |
Conductor
assembly |
Insulation
thickness
mm |
Screen
tape
mm |
Sheath
thickness
mm |
Overall
diameter
mm |
Weight
kg/km |
|
1×6mm2 |
7-stranded |
2.3 |
0.08 x 22 |
1.14 |
11.2 |
170 |
|
1×AWG8 |
7-stranded |
2.3 |
0.08 x 22 |
1.14 |
11.6 |
200 |
|
Cross-section mm2 |
Conductor resistance |
Voltage test
kV-min |
Insulation resistance MΩ.km@ 15.6 °C |
Partial discharge pC @ 4 kV |
|
1×6mm2 |
<3.11 |
35-15 |
>2220 |
<=5 |
|
1×AWG8 |
<2.18 |
35-15 |
>2060 |
<=5 |
Electrical characteristics:
Options:
- Different outer sheath colour (with consequently decreased UV resistance)
- Termite protected outer sheath
- Corrugated steel tape armour + bonded HDPE-sheath as rodent protection
- PVC outer sheath with flame retardance acc. to IEC 60332-1
Above types of
Airport lighting cable,We can manufacture for you. You are welcome to contact our cable engineers.
we manufacture andy power cable,If you need
overhead cable,For example acsr cale, aac cable,
abc cable...,please visit to
overhead cable site.