This is a kind of climate bearable PVC, HDPE and XLPE insulated aerial cables of copper core, aluminum core, or aluminum alloy core, suitable for overhead power lines of AC rated voltage Uo/U 0.6/1KV and below.
It is widely used in power transmission lines and electricity distribution lines with various voltage levels because they have such good characteristics as simple structure, convenient installation, and maintenance, and a low-cost large transmission capacity. And they are also suitable for laying across rivers valleys and places where special geographical features exist.
IEC 61089, BS 7870, DIN 48201, ASTM B399, BS EN50183, NFC33-209
Conductor: copper, aluminum, aluminum alloy
Insulation:PVC, HDPE, XLPE
Table 1 : Technology requirements of copper core ABC insulated cable
Nominal cross-section area of conductor(mm²) | Single wire Min. No of conductor | Conductor O.D.(reference value)/mm | Nominal thickness of insulation(mm) |
---|---|---|---|
10 | 6 | 3.8 | 1.0 |
16 | 6 | 4.8 | 1.2 |
25 | 6 | 6.0 | 1.2 |
35 | 6 | 7.0 | 1.4 |
50 | 6 | 8.4 | 1.4 |
70 | 12 | 10.0 | 1.4 |
95 | 15 | 11.6 | 1.6 |
120 | 18 | 13.0 | 1.6 |
150 | 18 | 14.6 | 1.8 |
185 | 30 | 16.2 | 2.0 |
240 | 34 | 18.4 | 2.2 |
The Max. Resistance of conductor at 20°C(Ω/km) | The Min, resistance of insulation at rated temperature | Breaking load of single core | ||
---|---|---|---|---|
Hard copper | Soft copper | 70°C | 90°C | Hard copper |
1.906 | 1.83 | 0.0067 | 0.67 | 3471 |
1.198 | 1.15 | 0.0065 | 0.65 | 5486 |
0.749 | 0.727 | 0.0054 | 0.54 | 8465 |
0.540 | 0.524 | 0.0054 | 0.54 | 11731 |
0.399 | 0.387 | 0.0046 | 0.46 | 16502 |
0.276 | 0.268 | 0.0040 | 0.40 | 23461 |
0.199 | 0.193 | 0.0039 | 0.39 | 31759 |
0.158 | 0.153 | 0.0035 | 0.35 | 39911 |
0.128 | 0.124 | 0.0035 | 0.35 | 49505 |
0.1021 | 0.0991 | 0.0035 | 0.35 | 61846 |
0.0777 | 0.0754 | 0.0034 | 0.34 | 79823 |
Table 2: Technology requirements of aluminum core, aluminum alloy core ABC insulated cable
No.section area of conductor (mm²) | Single wire Min. No Of conductor | Conductor O.D. (reference value)/mm | Cable Max. Average outer diameter(mm) |
---|---|---|---|
10 | 6 | 3.8 | 6.5 |
16 | 6 | 4.8 | 8.0 |
25 | 6 | 6.0 | 9.4 |
35 | 6 | 7.0 | 11.0 |
50 | 6 | 8.4 | 12.3 |
70 | 12 | 10.0 | 14.1 |
95 | 15 | 11.6 | 16.5 |
120 | 15 | 13.0 | 18.1 |
150 | 15 | 14.6 | 20.2 |
185 | 30 | 16.2 | 22.5 |
240 | 30 | 18.4 | 25.6 |
300 | 30 | 20.8 | 27.2 |
400 | 53 | 23.2 | 30.7 |
The Max. Resistance of conductor at 20°C (Ω/km) | The Min. resistance of insulation at rated temperature | Breaking load of single-core | |||
---|---|---|---|---|---|
Alumiunm | Aluminum alloy | 70°C | 90°C | Aluminum | Aluminum alloy |
3.08 | 3.574 | 0.0067 | 0.67 | 1650 | 2514 |
1.91 | 2.217 | 0.0065 | 0.65 | 2517 | 4022 |
1.20 | 1.393 | 0.0054 | 0.54 | 3762 | 6284 |
0.868 | 1.007 | 0.0054 | 0.54 | 5177 | 8800 |
0.641 | 0.744 | 0.0046 | 0.46 | 7011 | 12569 |
0.443 | 0.514 | 0.0040 | 0.40 | 10354 | 17596 |
0.320 | 0.371 | 0.0039 | 0.39 | 13727 | 23880 |
0.253 | 0.294 | 0.0035 | 0.35 | 17339 | 30164 |
0.206 | 0.239 | 0.0035 | 0.35 | 21033 | 37706 |
0.164 | 0.190 | 0.0035 | 0.35 | 26732 | 46503 |
0.125 | 0.145 | 0.0034 | 0.34 | 34679 | 60329 |
0.100 | 0.116 | 0.0033 | 0.33 | 43349 | 75411 |
0.0778 | 0.0904 | 0.0032 | 0.32 | 55707 | 100548 |
There is no news related to this product.
ZMS Cable have a wide product scope, includes: Power cables up to 500kV, AAC, AAAC, ACSR conductors, ABC Cable,electric wires, instrument cable, telecommunications cable, Stay wires. With advanced manufacture technology, rich human resource and effective management system, we guarantee all products are manufactured strictly in accordance with GB, IEC, BS, NFC, ASTM, DIN standards,etc. Beyond quality control, ZMS have been trying its best to offer much higher standard of services rather than expected.
You can contact us in the following ways:
email to sales@zmscable.com OR click Inquiry