Application
The quadruplex cables are suitable for use as drop cables from a pole-mounted transformer to the service entrance of a structure, or as the secondary distribution between poles. The cables should be limited to the voltages of 600 volts or less (phase to phase) at conductor temperatures not to exceed 75°C for polyethylene insulation conductors or 90°C for crosslinked polyethylene(XLPE) insulated conductors.
ASTM B230, B231, B232, B399, B498, ICEA S-76-474 Standard
The phase conductors are concentrically stranded compressed 1350-H19 aluminum and insulated polyethylene or crosslinked polyethylene (XLPE), The neutral messengers are concentrically stranded AAC, ACSR, or 6201 aluminum alloy. The conductors are manufactured with ridges for phase identification (one conductor with one ridge, one conductor with two ridges, and one conductor is plain).
(1)Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.
Code Name | Phase Conductor | Bare Neutral | Approx.Weight | Code Name | Phase Conductor | Bare Neutral | Approx. Weight | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Size | Stranding | Insulation Thickness | Size | Stranding | XLPE | PE | Size | Stranding | Insulation Thickness | Size | Stranding | XLPE | PE | ||
AWG | - | mil | AWG | - | lbs/1000ft | AWG | - | mil | AWG | - | lbs/1000ft | ||||
6201 Alloy Neutral Messenger | AAC Neutral Messenger | ||||||||||||||
Bay | 6 | Solid | 45 | 6 | 7 | 145 | 140.0 | Clydesdale | 4 | Solid | 45 | 4 | 7 | 208 | 201.8 |
French Coach | 6 | 7/w | 45 | 6 | 7 | 155 | 144.3 | Pinto | 4 | 7/w | 45 | 4 | 7 | 223 | 207.9 |
German Coach | 4 | Solid | 45 | 4 | 7 | 214 | 208.3 | Mustang | 2 | 7/w | 45 | 2 | 7 | 333 | 312.6 |
Arabian | 4 | 7/w | 45 | 4 | 7 | 229 | 214.4 | Criollo | 1/0 | 19/w | 60 | 1/0 | 7 | 529 | 504.5 |
Belgian | 2 | 7/w | 45 | 2 | 7 | 344 | 323.1 | Percheron | 2/0 | 19/w | 60 | 2/0 | 7 | 649 | 620.5 |
Shetland | 1/0 | 19/w | 60 | 1/0 | 7 | 546 | 521.1 | Hanoverian | 3/0 | 19/w | 60 | 3/0 | 19 | 799 | 765.6 |
Thoroughbred | 2/0 | 19/w | 60 | 2/0 | 7 | 670 | 641.5 | Oldenburg | 4/0 | 19/w | 60 | 4/0 | 19 | 986 | 946.7 |
Trotter | 3/0 | 19/w | 60 | 3/0 | 7 | 825 | 791.8 | Lippizaner | 336.4 | 19/w | 60 | 336.4 | 19 | 1,546 | 1,519.2 |
Walking | 4/0 | 19/w | 60 | 4/0 | 7 | 1019 | 979.7 | ||||||||
ACSR Neutral Messenger | |||||||||||||||
Morochuca | 6 | Solid | 45 | 6 | 6/1 | 152 | 147.4 | Grullo | 2/0 | 19/w | 60 | 2/0 | 6/1 | 707 | 678.7 |
Chola | 6 | 7/w | 45 | 6 | 6/1 | 162 | 151.7 | Suffolk | 3/0 | 19/w | 60 | 3/0 | 6/1 | 872 | 838.9 |
Morgan | 4 | Solid | 45 | 4 | 6/1 | 226 | 220 | Appaloosa | 4/0 | 19/w | 60 | 4/0 | 6/1 | 1079 | 1039.2 |
Hackney | 4 | 7/w | 45 | 4 | 6/1 | 241 | 226.1 | Bronco | 336.4 | 19/w | 60 | 336.4 | 18/1 | 1613 | 1568.2 |
Palomino | 2 | 7/w | 45 | 2 | 6/1 | 362 | 342.6 | Gelding | 336.4 | 19/w | 60 | 4/0 | 6/1 | 1548 | 1494.3 |
Costena | 1/0 | 19/w | 60 | 1/0 | 6/1 | 575 | 550.6 |
(2)Conductor temperature of 90°C for XLP, 75°C for poly; ambient temperatures of 40°C; emissivity 0.9; 2ft. / sec / wind in sun.
There is no news related to this product.
ZMS Cable have a wide product scope, includes: Power cables up to 500kV, AAC, AAAC, ACSR conductors, ABC Cable,electric wires, instrument cable, telecommunications cable, Stay wires. With advanced manufacture technology, rich human resource and effective management system, we guarantee all products are manufactured strictly in accordance with GB, IEC, BS, NFC, ASTM, DIN standards,etc. Beyond quality control, ZMS have been trying its best to offer much higher standard of services rather than expected.
You can contact us in the following ways: