sales@zmscable.com

12/20KV N2XSY Cable

6/10KV 12/20KV 18/30KV Copper Core XLPE Insulated PVC Sheath N2XSY Cable

Cable Construction

Circular bare copper-conductor of stranded wires to HD 383

Inner semi-conducting coating

Conductor insulation of cross-linked polyethylene (XLPE), PE-compound DIX8 to HD 620.1

Outer extrusion of semi-conducting coating spliced with the insulation

Wrapping of conductive material

Shield: Braiding of copper wires with one or two tape(s) applied helically

Wrapping

PVC outer jacket, compound DMV6 to HD 620.1

Jacket color: Red

Application

Suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground, and in water as well as for installation on cable trays for industries, switchboards, and power stations.

Due to the good laying characteristic, this cable can also be installed in difficult line guideways.

The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.

XLPE-insulated copper wire screen power cables to IEC 60502

Temperature Range

During installation up to -5°C/+23°F

Operating Temperature

Max. +90°C/+194°F

Short Circuit Temperature

+250°C/+482°F (short circuit duration up to 5 sec.)

Nominal Voltages

U0/U 6/10 kV, 12/20 kV, 18/30 kV

Operating Voltages for

6/10 kV = max. 12 kV

12/20 kV = max. 24 kV

18/30 kV = max. 36 kV

Test Voltages for

6/10 kV = 15 kV

12/20 kV = 30 kV

18/30 kV = 45 kV

Minimum Bending Radius

During Installation Max. 15x Cable Ø

Power Rating Table

See Technical Information


Technical characteristics:

NO. Cross- Section AreaCopper Wire Screen Area*NO. Sheath ThicknessNO. Overall DiameterApprox. Weight
N2XSY/ N2XSH CUN2XS2Y CUN2XS (F) 2Y CU
mm2mmmmmmkg / kmkg / kmkg / km
25161.82910009001100
35161.830110010501200
50161.831125011501350
70161.933150013501600
95161.934180016501900
120162.035215019002250
150252.037240022502500
185252.138280026002900
240252.142340032003500
300252.243400038004150
400352.344495047505100
500352.446605058006200
630352.550815080508300
800352.653960094509800


Power Cable

Power cables are used to transmit and distribute electrical energy. Power cables are commonly used in urban underground power grids, power station lead-out lines, power supply within industrial and mining enterprises, and over-the-river transmission lines.

There is no news related to this product.

CORPORATE SOCIAL RESPONSIBILITY

ZMS Cable have a wide product scope, includes: Power cables up to 500kV, AAC, AAAC, ACSR conductors, ABC Cable,electric wires, instrument cable, telecommunications cable, Stay wires. With advanced manufacture technology, rich human resource and effective management system, we guarantee all products are manufactured strictly in accordance with GB, IEC, BS, NFC, ASTM, DIN standards,etc. Beyond quality control, ZMS have been trying its best to offer much higher standard of services rather than expected.

The Adjuster
All customised cables designed by our cable engineer will be subject to testing to relevant standards and appropriate performance criteria. Bespoke cable testing will be conducted under our CNAS accreditation where appropriate. Where required by industry or application, we can submit for relevant cable certification and cable approval processes. For more information or to discuss possible custom designed cable solutions, please complete an enquiry form, contact our technical experts on the Technical Hotline +86 (0)371 6782 9333, or email:sales@zmscable.com

The Zms Cable Advantage

You can contact us in the following ways:

email to sales@zmscable.com OR click Inquiry

INQUIRY