NYBY Cable

NYBY cable are applied for power distribution in city networks, industrial plants and on the places where mechanical damages are expected. May be laid in the ground, cable ducts and in open air.
NYBY Cable

Application

Distribution power cable for static application, mostly in ground, but also in water, within facilities, in cable canals, in concrete. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants. Applied in conditions requiring protection against heavier mechanical damages, but where cables are not exposed to heavier tensile strain.


Standard

HRN HD 603 S1

IEC 60502-1

DIN VDE 0276 part 603

cables with 6 and more conductors:

HRN HD 627 S1

DIN VDE 027


Construction

Conductor:Cu, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295

class 1:solid, round (RE)

class 2:multi wire stranded, round (RM) or sector (SM), multi wire exceeding 50 mm² are compacted

Insulation:PVC compound, concentrically stranded cores, colour marked acc. to HRN HD 308 S2 / VDE 0293-308, with or without protective yellow-green conductor

Filler:spouted elastomer or plastomer compound or wrapped thermoplastic tapes

Armour:dtwo galvanized steel tapes

Sheath:PVC compound

sheath colour:black


Technical data

Temperature range: 

during installation:-5 °C up to +50 °C

fixed installed:-30 °C up to +70 °C

at short circuit of max. 5 s:up to 160 °C

Nominal voltage:Uο/U = 0,6/1 kV

Test voltage:4 kV

Maximal tensile strength:50 N/mm²

Behaviour in fire:IEC 60332-1

Minimal inner bending radius: 

single core:15D

multi core:12D


Special version upon request


Cross sectional area customized

Aluminum conductor required


Advantages

Excellent electric and mechanical characteristics

Best Resistance chemical corrosion and heat-ageing,environment stress and flame-retardant

Simple in structure,Convenient to use

Reduce costs


Dimensions and Weights


number of cores x conductor cross-sectionConstructionConstruction of individual conductorInsulation thicknessSheath thicknessExternal diameterCable weight
N x mm² N x mmmmmmmmKg/km
Power NYBY-J, NYBY-O
2 x 4RE1 x 2,211,815,3420
2 x 6RE1 x 2,711,816,3493
2 x 10RM7 x 1,3411,818,7668
2 x 16RM7 x 1,7011,820,9873
3 x 4RE1 x 2,211,816476
3 x 6RE1 x 2,711,817,1569
3 x 10RM7 x 1,3411,819,7783
3 x 16RM7 x 1,7011,822,11044
3 x 16+10RM/RE7 x 1,7/7 x 1,31,0 / 1,01,823,21163
3 x 25+16RM/RM7 x 2,2/7 x 1,71,2 / 1,01,826,21641
3 x 35+16SM/RM7 x 2,5/7 x 1,71,2 / 1,01,828,21978
3 x 50+25SM/RM7 x 3,/7 x 2,21,4 / 1,21,931,92606
3 x 70+35SM/RM13 x 2,7/7 x 2,51,4 / 1,2235,83471
3 x 95+50SM/RM17 x 2,7/7 x 31,6 / 1,42,242,64963
4 x 1,5RE1 x 1,370,81,814,2357
4 x 2,5RE1 x 1,740,81,815,1424
4 x 4RE1 x 2,211,817,1555
4 x 6RE1 x 2,711,818,3670
4 x 10RM7 x 1,3411,821,2936
4 x 16RM7 x 1,7011,823,81265
4 x 25RM7 x 2,201,21,8271793
5 x 4RE1 x 2,211,818,3640
5 x 16RM7 x 1,7011,825,81472
5 x 50SM7 x 3,001,42,1373498
5 x 70SM13 x 2,701,42,242,64956
5 x 95SM17 x 2,701,62,4506748
5 x 120SM18 x 3,001,62,653,17941


NYBY-JZ, NYBY-OZ

number of cores x conductor cross-sectionConstructionConstruction of individual conductorInsulation thicknessSheath thicknessExternal diameterCable weight
N x mm² N x mmmmmmmmKg/km
Signalnini NYBY-JZ, NYBY-OZ
6 x 4RE1 x 2,211,821,4800
7 x 4RE1 x 2,211,821,4830
8 x 4RE1 x 2,211,822,6930
10 x 4RE1 x 2,211,827,31125
12 x 4RE1 x 2,211,8271190
14 x 4RE1 x 2,211,829,31390
16 x 4RE1 x 2,212321850
19 x 4RE1 x 2,21233,42055
6 x 6RE1 x 2,711,822,5950
7 x 6RE1 x 2,711,822,51000
8 x 6RE1 x 2,711,8241125
10 x 6RE1 x 2,711,929,11350
12 x 6RE1 x 2,711,929,81510
14 x 6RE1 x 2,711,932,52015
16 x 6RE1 x 2,71233,72740
19 x 6RE1 x 2,712,135,52515