info@zmscable.com +86 371-67829-333

EPR Insulated AC Medium-voltage Submarine Cable

36kv xlpe submarine cable is used for transmit and distribute power in power transmission and distribution system of 36kV or lower.
EPR Insulated AC Medium-voltage Submarine Cable

Application

These submarine cables are used for power transmission to offshore islands, oil platforms or to cross-rivers and lakes. Cable design based on the mayor national or international standards e.g. VDE, IEC and ICEA or according to customers design and standards.

Standard

IEC 60228; IEC 60502;IEC 60840; IEC 62067

Construction

1.Conductor: Copper conductor, circular stranded compacted, water blocked.

2.Conductor Screening: Extruded semi-conductive compound.

3.Insulation: EPR.

4.Insulation Screening: Extruded semi-conductive compound.

5.Screen: Copper tapes.

6.Fillers: Polypropylene filler.

7.Separator: Binder tapes

8.Bedding Layer: Polypropylene strings.

9.Armour: Galvanized steel wires.

10.Serving: Hessian tapes, bituminous compound, polypropylene strings.

Electrical Data

6/10(12)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
350.270.37166
500.30.35197
700.340.33242
950.380.32289
1200.420.31328
1500.450.3367
1850.490.29402
2400.550.28469

12/20(24)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
350.190.41166
500.210.39197
700.240.37241
950.260.35288
1200.290.34327
1500.310.33365
1850.330.32409
2400.370.31470

18/30(36)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
500.170.43196
700.180.41241
950.20.39287
1200.220.37325
1500.230.36364
1850.250.35406
2400.370.31470

Dimension and Weight

6/10(12)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Screen Cross Section AreaNominal Bedding ThicknessNominal Steel Wire DiameterServing ThicknessOverall DiameterWeight
mm²mmmmmm²mmmmmmmmkg/m
3573.43x423.153.5565.4
508.23.43x423.153.5595.9
709.93.43x5.4243.5647.9
9511.53.43x5.4243.5689.1
120133.43x5.4243.57110.2
15014.53.43x6243.57411.4
18516.13.43x62.5548615
24018.63.43x62.5548716.7

12/20(24)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Screen Cross Section AreaNominal Bedding ThicknessNominal Steel Wire DiameterServing ThicknessOverall DiameterWeight
mm²mmmmmm²mmmmmmmmkg/m
3575.53x623.153.5656.8
508.25.53x623.153.5687.4
709.95.53x6243.5739.5
9511.55.53x6243.57710.7
120135.53x6243.58011.8
15014.55.53x6243.58313
18516.15.53x82549016.2
24018.65.53x82549518.5

18/30(36)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Screen Cross Section AreaNominal Bedding ThicknessNominal Steel Wire DiameterServing ThicknessOverall DiameterWeight
mm²mmmmmm²mmmmmmmmkg/m
508.283x623.153.5799.2
709.983x6243.58411.5
9511.583x8243.58812.8
1201383x8243.59114
15014.583x8243.59415.4
18516.183x1025410118.7
24018.683x1025410621.1