High voltage submarine cable

66kv Lead Sheathed AC submarine cable is Underground transmission of power cables,ZMS cable specializes in underground submarine cable power transmission.
High voltage submarine cable

Application

These submarine cables are used for power transmission to offshore islands, oil platforms or to cross-rivers and lakes. Cable design based on the mayor national or international standards e.g. VDE, IEC and ICEA or according to customers design and standards.

Standard

IEC 60228; IEC 60502;IEC 60840; IEC 62067

Construction

1.Conductor: Copper conductor, water blocked.

2.Conductor Screening: Extruded semi-conductive compound.

3.Insulation: XLPE.

4.Insulation Screening: extruded semi-conductive compound.

5.Separator: Swelling tape.

6.Core Sheath1: Lead Sheath.

7.Core Sheath2: Semi-conductive PE sheath.

8.Fillers: Polypropylene filler.

9.Fibre-optic Element: Fibre optic cable.

10.Separator: Binder tapes

11.Bedding: Bedding layer.

12.Armour: Galvanized steel wires filled with bitumen compound.

13.Serving: Polypropylene yarn.

Electrical Data

26/45(52)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
950.180.431.5
1200.190.421.6
1500.210.41.6
1850.220.391.8
2400.240.372
3000.260.362.2
4000.290.352.3
5000.320.332.6
6300.350.322.9
8000.380.313.1
10000.420.33.5

38/66(72.5)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
950.170.442
1200.180.432.1
1500.190.412.3
1850.20.42.4
2400.220.382.6
3000.240.372.8
4000.260.353.1
5000.290.343.5
6300.320.333.7
8000.350.324.1
10000.380.314.6

64/110(123)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
1850.140.462.8
2400.150.433
3000.170.413.5
4000.20.383.9
5000.220.374.3
6300.240.364.7
8000.260.345.2
10000.280.335.6

76/132(145)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
1850.130.473
2400.140.443.4
3000.160.423.8
4000.180.44.3
5000.20.384.6
6300.210.375.1
8000.230.365.6
10000.250.356.1

87/150(170)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
2400.130.473.4
3000.140.443.7
4000.150.424.1
5000.170.44.7
6300.190.385.3
8000.210.375.7
10000.230.366.3

127/220(245)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
5000.140.435.7
6300.160.416.4
8000.170.46.9
10000.190.387.4

160/275(300)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
5000.140.446.8
6300.160.427.7
8000.170.48.3
10000.180.399

Dimension and Weight

26/45(52)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Diameter Over InsulationNominal Lead Sheath ThicknessNominal Overall DiameterWeight
mm²mmmmmmmmmmkg/m
9511.2829.61.310920.8
12012.68311.311222.3
15014.2832.61.411624.4
18515.8834.21.411926.2
24018.1836.51.512429.5
30020.4838.81.613032.9
40023.2841.61.713637.9
50026.28451.814443.2
63029.8848.61.915249.7
80033.7852.52.116258.6
100037.9857.32.217368.1

38/66(72.5)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Diameter Over InsulationNominal Lead Sheath ThicknessNominal Overall DiameterWeight
mm²mmmmmmmmmmkg/m
9511.2931.61.311321.6
12012.69331.411623.8
15014.2934.61.412025.7
18515.8936.21.412428
24018.1938.51.612931.3
30020.4940.81.613434.3
40023.2943.61.714139.2
50026.29471.914945.4
63029.8950.6215752
80033.7954.52.116760.1
100037.9959.32.317870.7

64/110(123)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Diameter Over InsulationNominal Lead Sheath ThicknessNominal Overall DiameterWeight
mm²mmmmmmmmmmkg/m
18515.81650.2215640.9
24018.11550.5215742.5
30020.41450.8215744.1
40023.21351.6215947.2
50026.213552.116753
63029.81358.62.317660.7
80033.71362.52.418569.5
100037.91367.32.619780.5

76/132(145)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Diameter Over InsulationNominal Lead Sheath ThicknessNominal Overall DiameterWeight
mm²mmmmmmmmmmkg/m
18515.81854.22.116544.9
24018.11754.52.116646.3
30020.41654.82.116748
40023.21555.62.116851.1
50026.215592.317658
63029.81562.62.418565.2
80033.71566.52.519474
100037.91571.32.720685.4

87/150(170)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Diameter Over InsulationNominal Lead Sheath ThicknessNominal Overall DiameterWeight
mm²mmmmmmmmmmkg/m
24018.12162.52.418455.5
30020.42062.82.418557.3
40023.21963.62.418760.5
50026.218652.519065.1
63029.81766.62.519469.7
80033.71770.52.720479.8
100037.91775.32.821590.5

127/220(245)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Diameter Over InsulationNominal Lead Sheath ThicknessNominal Overall DiameterWeight
mm²mmmmmmmmmmkg/m
50026.22477.62.921981.3
63029.82379.2322486.7
80033.72383.13.123495.3
100037.92387.33.1241104

160/275(300)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Diameter Over InsulationNominal Lead Sheath ThicknessNominal Overall DiameterWeight
mm²mmmmmmmmmmkg/m
50026.22681.62.922984.7
63029.82481.2322888.9
80033.72485.13.123797.6
100037.92489.33.1247106.3