info@zmscable.com +86 371-67829-333

Medium voltage submarine cable

The XLPE Insulated & Sheathed 3 core submersible cables that we deal in are ideal for usage in submersible pumps in deep wells for irrigation (Direct Burial), drinking water supply, industries, mines, fountains.
Medium voltage submarine cable

Application:

These submarine cables are used for power transmission to offshore islands, oil platforms or to cross-rivers and lakes. 

Cable design based on the mayor national or international standards e.g. VDE, IEC and ICEA or according to customers design and standards.

Standard:

IEC 60228; IEC 60502;IEC 60840; IEC 62067

Construction:

1.Conductor: Copper conductor, circular stranded compacted, water blocked.

2.Conductor Screening: Extruded semi-conductive compound.

3.Insulation: XLPE.

4.Insulation Screening: Extruded semi-conductive compound.

5. Waterproof layer: semi-conductive waterproof tape

6.Screen: Copper wires and copper helix, swelling powder.

7.Laminated Core Sheath: Al. laminated tape bonded to overlaying 8.PE sheath

9.Fillers: Polypropylene filler.

10.Fibre-optic Element: Fibre optic cable.

11.Separator: Binder tapes.

12.Bedding Layer: Polypropylene strings.

13. Armour: Galvanized steel wires.

14.Serving: Hessian tapes, bituminous compound, polypropylene strings.


Electrical Data:

6/10(12)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
350.230.43167
500.260.41199
700.290.38241
950.320.37288
1200.350.35327
1500.380.34363
1850.420.33405
2400.470.32464

12/20(24)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
350.170.47171
500.180.44199
700.20.41243
950.220.4292
1200.240.38328
1500.260.37364
1850.280.35408
2400.310.34467

18/30(36)KV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
500.140.48202
700.150.45245
950.170.42291
1200.180.41330
1500.190.39366
1850.210.38411
2400.230.36470

Dimension and Weight


6/10(12)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Screen Cross Section AreaNominal Core Sheath ThicknessNominal Core DiameterNominal Bedding ThicknessNominal Steel Wire DiameterServing ThicknessOverall DiameterWeight
mm²mmmmmm²mmmmmmmmmmmmkg/m
3573.4162.52423.153.5707.5
508.23.4162.52523.153.5738.2
709.93.4162.527243.5779.9
9511.53.4162.528243.58011.1
120133.4162.530243.58412.2
15014.53.4252.531243.58713.6
18516.13.4252.5332549316.8
24018.63.4252.5352549919.1

12/20(24)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Screen Cross Section AreaNominal Core Sheath ThicknessNominal Core DiameterNominal Bedding ThicknessNominal Steel Wire DiameterServing ThicknessOverall DiameterWeight
mm²mmmmmm²mmmmmmmmmmmmkg/m
3575.5162.52823.153.5788.8
508.25.5162.53023.153.5839.3
709.95.5162.531243.58711.4
9511.55.5162.533243.58912.7
120135.5162.5342449414.1
15014.55.5252.5362449715.3
18516.15.5252.53725410218.6
24018.65.5252.54025410821.1

18/30(36)KV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal Screen Cross Section AreaNominal Core Sheath ThicknessNominal Core DiameterNominal Bedding ThicknessNominal Steel Wire DiameterServing ThicknessOverall DiameterWeight
mm²mmmmmm²mmmmmmmmmmmmkg/m
508.28162.53523.153.59311.1
709.98162.5362449912.8
9511.58162.53824410214.9
120138162.53924410516.2
15014.58252.54124410817.6
18516.18252.54225411321
24018.68252.54525411923.4