Welcome to ZMS Cable Email: info@zmscable.com Tel: +86 371-67829-333

H07RN-F

Low voltage 3 core rubber insulated flexible wire h07rn-f 3g1.5 rubber cable 3x1.5

H07RN-F

Specification:

Model: H07RN-F YC/YCW

Voltage: 300/500v,450/750v

Conductor Material: Copper

Insulation Material: Ethylene propylene rubber

Jacket Material: Natural rubber/Chloroprene rubber

Conductor Type: Soft Conductor

Operating temperature: Cable conductor long-term maximum allowable working temperature of 65 ℃; short circuit, the cable conductor maximum temperature does not exceed 160 ℃, the duration of not more than 5S.

Environmental Temperature: The cable runs at a minimum ambient temperature of -10 ° C..

Laying temperature: Installation laying, the temperature should not be less than -10 ℃.

Bending radius: Cable bending radius of not more than 10D..

Color: green / yellow, light blue, black, brown,or according to customer requirements

Application:

Super flexible cable can be fixedly laid in various environments such as indoor/outdoor, aerial, cable conduit or tunnel for power transmission and distribution line project, with rated A/C Uo/U being 450/750V or below. It widely used in outside small electric devices, agriculture electrification, construction lifts and gantries. And it is suitable for welder connection which is operates under Uo/U 220V.

H07RN-F Technical characteristics:


Dimensions – number of cores x conductor cross-section*

Construction of individual conductor

Conductor diameter

Insulation thickness

Sheath thickness

External diameter

Conductor resistance at 20 °C

Cu weight

Cable weight

Packing**


nominal

max.

nominal

nominal

min-max.

max.


approx.


N x mm²

n x mm

mm

mm

mm

mm

Ω/km

kg/km

kg/km


1 x 70

356 x 0,50

13

1,6

2,6

18,6 – 23,3

0,272

672

950

CUT

1 x 95

485 x 0,50

15,1

1,8

2,8

20,8 – 26,0

0,206

912

1202

CUT

2 x 1

32 x 0,20

1,5

0,8

1,3

7,7 – 10,0

19,5

19,2

105

CUT

3 G 1,5

30G0,25

1,8

0,8

1,6

9,2 – 11,9

13,3

43,2

162

c.100

4 G 4

56G0,30

3,2

1,0

2,0

14,0 – 17,9

4,95

153,6

402

CUT

4 G 6

84G0,30

3,9

1,0

2,3

15,7 – 20,0

3,30

230,4

561

CUT

5 G 4

56 x 0,30

3,2

1,0

2,2

15,6 – 19,9

4,95

192

470

CUT

5 G 6

84 x 0,30

3,9

1,0

2,5

17,5 – 22,2

3,30

288

620

CUT

12 G 1,5

30 x 0,25

1,8

0,8

2,9

17,6 – 22,4

13,3

172,8

560

CUT

19 G 1,5

30 x 0,25

1,8

0,8

2,5

22,5 – 26,6

13,3

273,6

795

CUT

24 G 1,5

30 x 0,25

1,8

0,8

3,5

24,3 – 30,7

13,3

345,6

1000

CUT

36 G 1,5

30 x 0,25

1,8

0,8

3,8

33,0

13,3

518,4


CUT


*) G = With protective yellow/green conductor, x = Without protective yellow/green conductor

**) Packing: c.100 = coil 100 m, CUT = cable in different lengths on drum or reel, possible cutting at required length

Next: ... Prev: ...